Partial discharge activity in distribution MOSAs due to internal moisture

Research output: Chapter in Book/Report/Conference proceedingConference contributionScientificpeer-review

Details

Original languageEnglish
Title of host publication2015 International Symposium on Lightning Protection (XIII SIPDA)
Place of PublicationBalneario Camboriu, Brazil
Pages94-98
VolumeXIII
ISBN (Electronic)978-1-4799-8753-5
DOIs
Publication statusPublished - 2 Oct 2015
Publication typeA4 Article in a conference publication
EventInternational Symposium on Lightning Protection - , United Kingdom
Duration: 1 Jan 2000 → …

Conference

ConferenceInternational Symposium on Lightning Protection
CountryUnited Kingdom
Period1/01/00 → …

Abstract

In order to evaluate if metal oxide surge arrester present any partial discharge (PD) in case of internal moisture and how applicable it is as a condition monitoring diagnostic method, 8 distribution class (Ucov = 20 kV) metal oxide surge arresters (6 silicone housed and 2 Ethylen-Vinylacetate (EVA) housed) from four different manufacturers (A, B, C and D) were submitted to an immersion test for 19 days. The partial discharge and leakage current levels were measured daily. Parameters like largest repeatedly occurring PD magnitude, discharge current and PD repetition rate were recorded for later comparison with power loss calculated from the leakage current. In some of the arresters internal moisture was noticed, however, partial discharge measurement was not as sensitive as power loss. For those samples identified with internal moisture, the partial discharge activity showed a special behavior keeping a limited amplitude itself but presenting a high repetition rate.

ASJC Scopus subject areas

Publication forum classification