Verifying the indication method for high-resistance earth faults implemented in centralized protection system
Research output: Chapter in Book/Report/Conference proceeding › Conference contribution › Scientific › peer-review
Standard
Verifying the indication method for high-resistance earth faults implemented in centralized protection system. / Nikander, Ari; Valtari, Jani; Raipala, Ontrei; Kettunen, Erkka.
22nd International Conference and Exhibition on Electricity Distribution, CIRED 2013. Vol. 2013 615 CP. ed. 2013. 1130.Research output: Chapter in Book/Report/Conference proceeding › Conference contribution › Scientific › peer-review
Harvard
APA
Vancouver
Author
Bibtex - Download
}
RIS (suitable for import to EndNote) - Download
TY - GEN
T1 - Verifying the indication method for high-resistance earth faults implemented in centralized protection system
AU - Nikander, Ari
AU - Valtari, Jani
AU - Raipala, Ontrei
AU - Kettunen, Erkka
PY - 2013
Y1 - 2013
N2 - The paper presents verifying test results of the primary substation level centralized functionality in laboratory. The attention is concentrated to verifying the indication method for high-resistance phase-to-earth faults in neutral isolated and compensated networks. The applied method is based on the studies and results carried out in TUT. For properly testing the test environment needed to be set up for centralized functionality. This environment was set up in TUT and it utilizes the Real Time Digital Simulator (RTDS®). The indication method for high-resistance earth faults has been implemented as centralized in order to test the new technology. It utilizes new possibilities of the centralized protection system. The essential method in this study was RTDS simulations of centralized protection system.
AB - The paper presents verifying test results of the primary substation level centralized functionality in laboratory. The attention is concentrated to verifying the indication method for high-resistance phase-to-earth faults in neutral isolated and compensated networks. The applied method is based on the studies and results carried out in TUT. For properly testing the test environment needed to be set up for centralized functionality. This environment was set up in TUT and it utilizes the Real Time Digital Simulator (RTDS®). The indication method for high-resistance earth faults has been implemented as centralized in order to test the new technology. It utilizes new possibilities of the centralized protection system. The essential method in this study was RTDS simulations of centralized protection system.
UR - http://www.scopus.com/inward/record.url?scp=84897704661&partnerID=8YFLogxK
U2 - 10.1049/cp.2013.1130
DO - 10.1049/cp.2013.1130
M3 - Conference contribution
SN - 9781849197328
VL - 2013
BT - 22nd International Conference and Exhibition on Electricity Distribution, CIRED 2013